논문명 클린룸 청정도 유지를 위한 최적 차압도출/The Suitable Positive Pressure for Cleanliness in a Clean Room/2 사례발표
저자명 이창수 ; 장창익
발행사 한국건축친환경설비학회
수록사항 추계학술발표대회  , 2007
페이지 시작페이지(41) 총페이지(5)
주제분류 환경및설비
주제어 클린룸 ; 양압 ; 청정도 ; clean room ; positive pressure ; pressure difference
요약2 The purpose of this study is to deduce the suitable positive pressure for cleanliness in a clean room. As the constant air volume is exhausted, the pressure difference is compared and analyzed between clean room and outdoor. As a result, the suitable positive pressure is 1.2 mmAq ~ 1.5 mmAq, which can cause the saving of power consumption compared with current operating pressure difference.