논문집

원문다운로드
논문명 제로에너지건축물 인증을 고려한 데이터센터의 최적 지역 선정 연구/A Study on the Selection of the Optimal Region of Data Center Considering Zero Energy Building Certification
저자명 이도형(Lee, Do-Hyung) ; 변수영(Byun, Soo-Young)
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집  , Vol.15 No.4
페이지 시작페이지(375) 총페이지(11)
ISSN 1976-6483
주제분류 환경및설비
주제어 데이터센터; 제로에너지 건축물; 1차 에너지소비량; 에너지자립률 Data center; Zero energy building; Primary energy consumption; Energy independence rate
요약2 Using the building energy efficiency rating evaluation program, this study analyzed the optimal region in terms of energy independence rate of data centers in 66 regions in Korea. Pyeongchang has the most advantageous energy consumption and Changwon has the most disadvantageous analysis, which is believed to have a greater impact on ambient air temperature than solar radiation. A 19.53% difference occurred as Pyeongchang was the most advantageous with an energy independence rate of 67.76%, and Jeju was the most unfavorable with an energy independence rate of 48.23%. In addition, Pyeongchang is the only one among all regions to be able to acquire building energy efficiency rate for grades 1+++. The smaller the primary energy consumption per unit area, the more advantageous it is to energy independence rate, so it is believed that the data center should consider selecting optimal areas, optimal heat sources, and equipment placement considering ambient temperature.
소장처 한국건축친환경설비학회