논문명 |
편복도형 교실내 환기방식에 따른 미세먼지 저감효과 분석/Analysis of PM10 Reduction Effect by Ventilation Method in One Side Corridor Type Classroom |
저자명 |
차대오(Cha, Dae-O) ; 이인호(Lee, In-Ho) ; 김병수(Kim, Byung-Soo) ; 황정하(Hwang, Jung-Ha) |
발행사 |
한국건축친환경설비학회 |
수록사항 |
한국건축친환경설비학회 논문집
,
Vol.14 No.3
|
페이지 |
시작페이지(233) 총페이지(14)
|
ISSN |
1976-6483 |
주제분류 |
환경및설비
|
주제어 |
편복도형 교실; 미세먼지(PM10); 환기방식; 시뮬레이션; 저감효과 One side corridor type classroom; PM10; Ventilation Type; Simulation; Reduction effect
|
요약2 |
Depending on the particulate matter (PM) concentration in the outdoor air, this study investigated the effects of ventilation method on reducing the PM in classrooms via simulation; PM concentration changes were measured and analyzed in the one side corridor type classroom.
The outdoor air PM concentration levels were divided into good (30 μg/㎥), normal (60 μg/㎥), and bad (150 μg/㎥). Four cases were identified based on the ventilation method: window open [C-1], with window-mounted air filter installed [C-2], EHP operation combined with the ventilation system [C-3], and the operation of floor-type air purifier [C-4]. The simulation was performed using STAR-CCM+(ver.11.06). Simulation results showed that in [C-1], the outdoor PM concentration were reduced and depicted good level in outdoor air PM concentration level is good. [C-2] and [C-3] showed up to 16.2% increase and 22% decrease, respectively, in PM reduction efficiency compared to [C-1]. Finally, [C-4] showed up to 16% increase in the PM reduction efficiency in comparison to [C-1], demonstrating excellent PM reduction effect. |
소장처 |
한국건축친환경설비학회 |