논문집

원문다운로드
논문명 유전알고리즘을 이용한 중앙공조시스템 냉수배관계의 최적제어 방법/Determination of Optimal Variables for Chilled Water Loop in Central Air-conditioning System using Genetic algorithms
저자명 성남철(Seong, Nam-Chul) ; 김지헌(Kim, Jee-Heon) ; 최원창(Choi, Won-Chang)
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집  , Vol.14 No.1
페이지 시작페이지(66) 총페이지(14)
ISSN 1976-6483
주제분류 환경및설비
주제어 냉수시스템; 냉수공급온도; 펌프차압; 최적제어; 유전알고리즘 Chilled water system; Supply chilled water temperature; Pump pressure difference; Optimal control; Genetic algorithm
요약2 This paper suggests the real-time optimal control method of central air-conditioning system using chilled water. The control variables for optimization are differential pressure of the pump and the supply chilled water temperature supplied to the air conditioning system produced from the central chiller. The optimal control variables of the control point are calculated using genetic algorithm in one-hour time step. The objective function of algorithm was the energy consumption of the HVAC system, and the energy consumption was calculated using the mathematical model. The results of the operation of the normal mode under the initial design conditions and the optimal operation mode with the optimal control variables were evaluated by comparing the energy consumption of the HVAC system with the variation of the control volume at the control point selected in this study. As a result, the chilled water supply temperature of the chilled water loop was operated by changing between approximately 9°C and the differential pressure of the pump between 34.87 kPa and 78.91 kPa for the optimal control method. The total energy consumption of the HVAC system during optimal control operation was reduced by 16.98% compared to operation of the normal mode.
소장처 한국건축친환경설비학회