논문집

원문다운로드
논문명 공공기관 사무소 건물의 흡수식 냉온수기 대수제어에 따른 하절기 에너지절감 효과에 관한 연구/A Study on the Effects of Energy Savings from the Sequential Controls of Absorption Chiller-heaters for Public Office Buildings in Summer
저자명 김상준(Kim, Sang-Jun) ; 송수원(Song, Su-Won)
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집  , Vol.13 No.6
페이지 시작페이지(536) 총페이지(9)
ISSN 1976-6483
주제분류 환경및설비
주제어 흡수식 냉온수기; 성적계수; 순차제어; 에너지절감 Absorption chiller-heaters; coefficient of performance; sequential operation; energy savings
요약2 Absorption chiller-heaters have widely been used for cooling and heating in public buildings, due to government energy policy in Korea since 1980s. However, the sequence of operations for such absorption chiller-heaters with different capacity and efficiency has not been sufficiently studied under actual operational conditions. This study analyzed the effects of energy savings from the sequential controls of absorption chiller-heaters for a public office building using calibrated energy simulation with measured data in summer. As a result, it is found that the proposed sequential operations with a prorate load control of three absorption chiller-heaters is expected to save cooling energy (e.g., gas consumption) about 17% for the case-study building. Therefore, it is recommended that the sequential operations of absorption chiller-heaters should be coupled with equipment efficiency and capacity to effectively improve overall operational efficiency and save energy.
소장처 한국건축친환경설비학회