논문명 실별 바닥 마감재 차이를 고려한 바닥난방 시스템의 온수유량 조절 효과/Adjustment Effect of Water Flow Rate for Floor Heating System considering the Difference in Floor Covering of Individual Room
저자명 이규남(Rhee, Kyu-Nam) ; 김종현(Kim, Jong-Hyun) ; 김광명(Kim, Kwang-Myung) ; 김범수(Kim, Bum-Soo) ; 정근주(Jung, Gun-Joo)
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집  , Vol.13 No.4
페이지 시작페이지(258) 총페이지(12)
ISSN 1976-6483
주제분류 환경및설비
주제어 바닥 마감재; 바닥난방; 바닥표면온도; 실온; 온수유량 Floor covering; Floor heating; Floor surface temperature; Room air temperature; Water flow rate
요약2 In this study, the impact of floor coverings on the behavior of floor surface and room air temperature was investigated through mock-up experiment and energy simulation. The results showed that temperature unbalance between each room can be caused by different floor covering material. PVC flooring showed the fastest speed of temperature rise and descend, followed by VCT (Vinyl composite tile), wood and porcelain tile. It was found that the rise time is related with the heat capacity and thermal resistance, which were analyzed based on the heat balance equation. Thus, it was suggested to adjust water flow rate considering the heat capacity and thermal resistance of floor covering, in order to minimize the temperature unbalance in each room and the probable thermal discomfort. The augmented flow rate resulted in the reduced rise time in the room with massive floor covering such as porcelain tile, which was also effective in mitigating the temperature unbalance in each room. In addition, it was found that the rise time and temperature unbalance can be more reduced by resetting the augmented flow rate to design flow rate, if room air temperature approaches its set-point temperature.