Increased density of racks has resulted in increased use of data center cooling energy and the needs for energy efficient cooling systems has increased. In response to these needs, ASHRAE presented a performance indicator, which is Mechanical Load Component (MLC), for the purpose of evaluating systems at the design stage. However, the MLC metrics presented in the current standard can only be determined for system compliance and compared alternative systems with the system configuration completed. Therefore, there are limitations to considering MLC from the early stages of design. In this study, to extend the scope of application of MLC in the design phase, the design factors of the main equipment comprising the cooling system are classified by the MLC load component and interrelations between design factors were identified. |