논문명 2차원 전열해석을 통한 천장거치형 흡음 패널의 설계조건에 따른 TABS의 방열 특성 평가/Evaluation of Free Hanging Acoustic Panel Design on the Cooling Characteristic of Thermally Activated Building System Through Two Dimensional Heat Transfer Analysis
저자명 이윤선(Lee, Yoon-Sun) ; 임재한(Lim, Jae-Han) ; 정웅준(Chung, Woong-June)
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집  , Vol.12 No.2
페이지 시작페이지(159) 총페이지(12)
ISSN 1976-6483
주제분류 환경및설비
주제어 구체축열시스템 ; 냉방 성능 ; 천장거치형 흡음 패널 Thermally activated building system ; Cooling performance ; Free hanging acoustic panel
요약2 Low temperature heating and high temperature cooling systems have proven to be an energy efficient solution for conditioning building. Thermally activated building system (TABS) has become established as innovative systems for radiant heating and cooling system, and utilizes the building structure to store the thermal energy, reduce the peak loads and decrease primary energy demand in buildings. However, room acoustic performance should be of concern for the use of TABS. For this, free hanging acoustic panels (FHAP) were generally designed to reduce the overall sound intensity and reverberation time. This study aims to investigate the long-term effect of FHAP on cooling performance characteristics of TABS through two dimensional heat transfer simulation. In results, the coverage ratio up to 50% of the ceiling area by using horizontal FHAP has no significant influence on the cooling performance characteristics. And the vertical FHAP does not affect the cooling capacity from the ceiling at all.
소장처 한국건축친환경설비학회