논문명 |
노후 바닥 난방 배관 내 스케일 제거에 의한 실내 난방온도 상승 및 에너지 저감 효과에 관한 연구/A Study on Improvement of Heating Effect by Removing Internal Scale of Floor Heating System |
저자명 |
임민엽(Rim, Min-Yeop) ; 홍승훈(Hong, Seun-ghun) |
발행사 |
한국건축친환경설비학회 |
수록사항 |
한국건축친환경설비학회 논문집
,
Vol.11 No.6
|
페이지 |
시작페이지(527) 총페이지(9)
|
ISSN |
1976-6483 |
주제분류 |
환경및설비
|
주제어 |
배관스케일 ; 바닥복사난방 ; 실내 난방온도 ; 난방에너지소비량 Pipe Scale ; Radiant Floor Heating ; Indoor Heating Temperature ; Heating Energy Consumption
|
요약2 |
This paper presents the improvement of heating effect after removing internal scale of old heating system. The air temperature of chamber was increased maximum 2.4°C, floor surface temperature increased 2.6°C. According to the TRNSYS simulation, the conductivity of system increased 0.088 W/m·k. When calculated using 84m2 apartment model by TRNSYS simulation, annual heating energy consumption decreased about 7.86kWh/m2, 6.2%. |