논문집

원문다운로드
논문명 종합병원내 공기감염 예방을 위한 진료부와 로비공간의 기류 분석/Airflow Analysis in Policlinic and Lobby Space for Prevention of Airborne Infection in General Hospitals
저자명 송해은(Song, Hae-Eun) ; 원안나(Won, An-Na) ; 김성용(Kim, Seong-Yong) ; 박진철(Park, Jin-Chul) ; 황정하(Hwang, Jung-Ha)
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집  , Vol.11 No.5
페이지 시작페이지(453) 총페이지(12)
ISSN 1976-6483
주제분류 환경및설비
주제어 공기감염예방 ; 진료부와 로비공간 ; 급 · 배기구 위치 ; 개선안제시 Airborne Infection ; Policlinic and Lobby space ; air-inlet and outlet position ; improvement suggestion
요약2 This study analyzes the types of space in the polyclinic and lobby spaces of hospitals, which are thought to be exposed to secondary airborne infections within hospitals. A hospital, which has space where the human traffic from the polyclinic overlaps with that of the lobby (space type II), was selected as the subject of this study. The air current distribution in the polyclinic and lobby areas are analyzed using the calculation program Star-ccm+. The air current distribution in the existing air-conditioned space is analyzed using T · A · B (Testing, Adjusting, Balancing) measured values. The result proved the possibility of secondary airborne infections caused by mixing of the air currents from the polyclinic and lobby in the upper and middle air layers. Five improvement suggestions in terms of changing the position of air inlets and outlets are proposed in this study. Among them, [ALT-3] the arrangement wherein outlets are placed on the first and third lines and inlets are placed on the second line is expected to significantly reduces the possibility of airborne infections, as the air currents in the lower, middle, and upper layers in the polyclinic and lobby spaces are not intermixed.
소장처 한국건축친환경설비학회