논문집

원문다운로드
논문명 공동주택 평면 형태에 따른 하부세대 인접실의 급배수 소음 전달 특성에 대한 실험적 연구/An Experimental Study on Sound Attenuation Characteristics of Plumbing Noise in the Apartment Bathroom to Neighbouring Space according to Unit Plan
저자명 조현민(Hyun-Min Cho) ; 양홍석(Hong-Seok Yang) ; 김명준(Myung-Jun Kim)
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집  , Vol.11 No.3
페이지 시작페이지(219) 총페이지(11)
ISSN 1976-6483
주제분류 환경및설비
주제어 공동주택 ; 평면 형태 ; 욕실 급배수 소음 ; 공기전달음 ; 전달 감쇠 ; 하부세대 인접실 ; 문 개폐 여부 Apartment ; Unit Plan ; Plumbing Noise ; Airborne Sound ; Sound Attenuation ; Neighboring space ; Door Opening Conditions
요약2 In this study, field measurements were carried out in 17 bathrooms of 10 housings with different floor plans to investigate the level of the plumbing noise transmitted from the bathroom to the neighboring space according to the door opening conditions. The noise reduction at the neighboring space relative to the noise level in the bathroom was analyzed by focusing on the drainage noise of the water closet showing higher noise level than other sanitary wares. The result showed that the noise level in the bathroom with the open door decreased by about 2.1 dB(A) compared to the closed door due to the increased sound absorption. Compared to the noise level in the UBR bathroom, the noise reduction in front of the door was analyzed to be 6.1 dB(A) and 1.1 dB(A) in the closing and opening conditions, respectively. On the other hand, the noise reduction for the bathroom applying wet construction method was 11.4 dB(A) and 6.1 dB(A) in the door closing and opening conditions, respectively. Due to the above result, the noise level in the adjacent room is similar between both construction methods, although UBR system showed lower noise level in the bathroom than wet construction method. This is due to the contribution of the flanking transmission noise on determining the overall noise level, which is also confirmed by the measurement for airborne sound insulation using a speaker. The result indicates that the flanking transmission noise needs to be controlled to reduce overall level of the plumbing noise in the neighboring space.
소장처 한국건축친환경설비학회