논문명 고층건물에서 수직샤프트 계획에 따른 침기량 평가/An Evaluation of Infiltration Rate according to Vertical Shaft Plan in High-rise Buildings
저자명 신현국(Shin, Hyun-Kook) ; 윤현정(Yoon, Hyun-Jung) ; 지경환(Ji, Kyung-Hwan) ; 조재훈(Jo, Jae-Hun)
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집  , Vol.10 No.1
페이지 시작페이지(47) 총페이지(8)
ISSN 1976-6483
주제분류 환경및설비
주제어 침기량 ; 고층건물 ; 외피압력차 ; 수직샤프트 Infiltration Rate ; High-rise Building ; Pressure Difference Across the Building Envelope ; Vertical Shaft
요약2 It is difficult to predict the air volume of the infiltration which is uncontrolled air entering through building envelope. In high-rise buildings, pressure differences of building envelope vary with building height, temperature differences between indoor and outdoor, and building characteristics. Especially, stack-induced huge pressure difference occurs in winter season. However, there is no consideration of stack effect in an conventional load calculation method for deciding capacity of HVAC system. The calculation result may have large difference to a actual building. The purpose of this paper is to suggest a simplified calculation method of infiltration by taking account of stack effect in a high-rise building in winter, considering the infiltration change according to vertical shaft plan. Affecting factors for infiltration in high-rise building were investigated and a simplified method of calculating infiltration was suggested. As a simulation result of 3 different vertical shaft type, it is shown that Neutral Pressure Level(NPL) and Thermal Draft Coefficient(TDC) vary from vertical shaft design plan. Accordingly, NPL height and TDC value are the factors that have a significant effect on infiltration. The infiltration calculation was performed by using the proposed simplified method, targeting single zone type and multiple zone type.
소장처 한국건축친환경설비학회