논문집

원문다운로드
논문명 외기전담시스템의 병원건물에 대한 적용성 및 냉난방 에너지 절감 효과에 관한 연구/Applicability and Air-Conditioning Energy Saving Potentials of a Dedicated Outdoor Air System in a Healthcare Facilities
저자명 김민휘 ; 김진효 ; 권오현 ; 석윤진 ; 정재원
발행사 한국건축친환경설비학회
수록사항 한국건축친환경설비학회 논문집  , v.3 n.4
페이지 시작페이지(184) 총페이지(8)
주제분류 환경및설비
주제어 외기전담시스템 ; 병원 ; 병실환기 ; 정풍량공조 ; 변풍량공조 ; DOAS ; Health care facilities ; Patient room ventilation ; CAV ; VAV
요약2 The purpose of this paper is to investigate supply air conditions and energy saving potentials of a dedicated outdoor air system (DOAS) applied to a patient room of health care facilities. The design of HVAC systems for healthcare facilities is a specialized field of engineering. Based on the current health care facilities design satandards, it was assumed that four 25.8m2 unit patient rooms are served by the three different HVAC systems; a constant air volume system(CAV) with fan coil unit(FCU), a variable air volume system (VAV), and a dedicated outdoor air system (DOAS) with fan coil unit (FCU). Control strategies and energy saving potentials of each system were modeled and estimated using the TRNSYS 16 energy simulation program. Annual cooling and heating coil loads and fan energy reduction were calculated. It was found that the DOAS+FCU system can reduce the fan energy consumption over 65% annually compared with the conventional CAV+FCU system. In addition, over 57.5% of annual cooling coil load can be reduced by use of DOAS+FCU system.
소장처 한국건축친환경설비학회