배기구 위치의 차이에 의한 병실 공기 청정도 검토/Examination of Air Clearness in Sickroom by Difference of Exhaust Opening position |
저자명 |
양정훈 |
발행사 |
한국건축친환경설비학회 |
수록사항 |
한국건축친환경설비학회 논문집
,
v.2 n.1
|
페이지 |
시작페이지(8) 총페이지(7)
|
주제분류 |
환경및설비
|
주제어 |
병실공조 ; 공기질 ; 인체주변기류 ; CFD ; Air-Conditioning in Hospital ; Air Quality ; Airflow around Human Body
|
요약2 |
The aim of this paper is to examination of air clearness by difference of exhaust opening position in sickroom which is accepted central air-conditioning system. The examination was used Computational Fluid Dynamic (CFD). The result is that 1 or 2 exhaust opening at ceiling was good ventilation efficiency better than 4 exhaust opening at ceiling or floor in same airflow amount. If the exhaust opening install in around floor, the ventilation efficiency become wrong by bed or curtain obstructing airflow |